34
09 (U) Setup1*
* Cannot be
written to RAM
Bit 7 6 5 4 3 2 1 0
0 0 4-1/2 digit display (0.1° temp.)
0 1 Remote display
1 0 4-1/2 digit count by 10 (0.01° t.)
1 1 3-1/2 digit display (1° temp.)
0D (U) Alarm Confg4 Bit 7 6 5 4 3 2 1 0 Alarm Trigger Delay
60 Hz 50Hz
0 0 0 0.018 s 0.021 s
0 0 1 0.035 0.043
0 1 0 0.07 0.085
0 1 1 0.14 0.17
1 0 0 0.28 0.34
1 0 1 0.56 0.68
1 1 0 1.13 1.36
1 1 1 2.27 2.72
0 0 0 Al3 Band Dev, Al4 Band Dev
0 0 1 Al3 Hysteresis, Al4 Band Dev
0 1 0 Al3 Band Dev, Al4 Hysteresis
0 1 1 Al3 Hysteresis, Al4 Hysteresis
1 0 0 No deviation in menus or calc
0C (U) Alarm Confg3 Bit 7 6 5 4 3 2 1 0
0 0 0 0 Al3 Hi active, Al4 Hi active
0 0 0 1 Al3 Lo active, Al4 Hi active
0 0 1 0 Al3 Disabled, Al4 Hi active
0 1 0 0 Al3 Hi active, Al4 Lo active
0 1 0 1 Al3 Lo active, Al4 Lo active
0 1 1 0 Al3 disabled, Al4 Lo active
1 0 0 0 Al3 Hi active, Al4 disabled
1 0 0 1 Al3 Lo active, Al4 disabled
1 0 1 0 Al3 disabled, Al4 disabled
0 0 Al3 non-latch, Al4 non-latch
0 1 Al3 latch, Al4 non-latch
1 0 Al3 non-latch, Al4 latch
1 1 Al3 latch, Al4 latch
0 0 Relay3 On when Al3 active, Relay4 On when Al4 active
0 1 Relay3 Off when Al3 active, Relay4 On when Al4 active
1 0 Relay3 On when Al3 active, Relay4 Off when Al4 active
1 1 Relay3 Off when Al3 active, Relay4 Off when Al4 active