6.2 FRONT PANEL SETUP, COUNTERS & TIMERS ONLY
Press Menu
Select Key
Press Digit Select
Key
Press Value Select Key
___000
Output filtering
0 Send unfiltered signal
1 Send filtered signal
___000U
Baud rate
0 300 baud 4 4800 baud
1 600 baud 5 9600 baud
2 1200 baud 6 19200 baud
3 2400 baud
. Ser 1.
Serial Setup 1.
Press until
Ser 1
is displayed.
Fixed Parameters
- No parity
- 8 data bits
- 1 stop bit
___000U
Output update rate,
Continuous Data Output
Mode.
60 Hz 50 Hz
0 0.017 sec 0.020 sec
1 0.28 sec 0.34 sec
2 0.57 sec 0.68 sec
3 1.1 sec 1.4 sec
4 2.3 sec 2.7 sec
5 4.5 sec 5.4 sec
6 9.1 sec 10.9 sec
7 18.1 sec 21.8 sec
8 36.6 sec 43.5 sec
9 72.5 sec 97 sec
__0000U
Line feed
0 No <LF> after <CR>
1 <LF> after <CR>
__0000U
Alarm data with readings
0 No alarm data
1 Alarm data with reading
__0000U
Control of data output
0 Continuous data output
1 Data output on ASCII command only
. Ser 2.
Serial Setup 2
__0000U
Meter address with Custom
ASCII protocol
Select 1 thru F for addresses 1 thru 15.
Select 0. thru F. (with decimal point) for
addresses 16 thru 31.
. Ser 3.
Serial Setup 3
_00000U
RS485 half or full duplex
0 Full duplex
1 Half duplex
_00000U
Special start & stop char.
(entered using Instrument
Setup Software)
0 Standard continuous mode
1 Special start & stop characters